Hi Everyone. Well, after 15 years the RV-Dreams Community Forum is coming to an end. Since it began in August 2005, we've had 58 Million page views, 124,000 posts, and we've spent about $15,000 to keep this valuable resource for RVers free and open. But since we are now off the road and have settled down for the next chapter of our lives, we are taking the Forum down effective June 30, 2021. It has been a tough decision, but it is now time.
We want to thank all of our members for their participation and input over the years, and we want to especially thank those that have acted as Moderators for us during our amazing journey living and traveling in our RV and growing the RV-Dreams Family. We will be forever proud to have been founders of this Forum and to have been supported by such a wonderful community. Thank you all!!
Seriously, my power cable is about 50 feet short of an electrical box located in my back yard. Trailer is parked in front of the house. I can either purchase a couple of 30 feet extension cables or install a 50 amp recepticle about 60 feet away from electrical panel. The extra lenght here is due to conduit running along the side of the house
My concern is size of wiring leading to 50 amp recepticle. 4AWG is difficult to get, 6AWG is readily available.
Of course I can hire an electrician and solve the problem.
__________________
Jerry & Carol Pearson (+ fur babies) FullTime since 2012 04 Winnebago Adventure, 06 Grand Marquis www.waggintailsrv.com
Seriously, my power cable is about 50 feet short of an electrical box located in my back yard. Trailer is parked in front of the house. I can either purchase a couple of 30 feet extension cables or install a 50 amp recepticle about 60 feet away from electrical panel. The extra lenght here is due to conduit running along the side of the house
My concern is size of wiring leading to 50 amp recepticle. 4AWG is difficult to get, 6AWG is readily available.
Of course I can hire an electrician and solve the problem.
Having one 30 ft extension might come in handy at another time. Two? I don't thiink I would go that route. Besides, having an exposed connection that you would have to protect in case of heavy rain might not be best. I think I might go with the hire an electrician. I betcha he can get the correct size, and besides that, he would do all the sweating. It is supposed to crack 100 deg here today, gotta be hot in Corpus.
I think I'd hire the electrician and have him put in a power pedestal close to the RV like you'd have in a campground. Depends on how far you are from your main panel box as far as line loss is concerned. You may need a subpanel box to reduce the voltage loss because of the length of the circuit.
__________________
Ron and Joan 2005 Itasca Sunova 34A 2004 Jeep Grand Cherokee Overland
A lot of people wire in two 30AMP circuits and use a "cheater box" to combine them into a 50AMP plug, where you can get away with more reasonable wire gauges. In most cases only having 30AMPs per leg will be OK, in our case we can't run the electric hot water heater, front air and washer/dryer at the same time and have to limit ourselves to one large kitchen appliance when the rear air is running. Camping World and other places have the cheater boxes. Having two 30AMP plugs lets you share with friends.
__________________
Bill Joyce, 40' 2004 Dutch Star DP towing an AWD 2020 Ford Escape Hybrid Journal at http://www.sacnoth.com Full-timing since July 2003
If you can get the proper sized wiring to the location, keep in mind that 2-30 amp services = 60 amps available whereas 1-50 amp service = 100 amp available.
-- Edited by Bill Adams on Sunday 8th of May 2011 09:27:36 AM
I'll call electrician Monday and see what he says. Unless he want an arm and leg, I'll let him sweat the details. I am not keen on the idea of more than one extension. Ken temperature reached mid 90's in Corpus today. With the afternoon sun hitting the RV, it warmed up pretty quick in there today. With all the sun we've had, I should solar panel the roof and add extra storage batteries. Time to read Jack Mayer's discussion on this topic. Bill - Thanks, I understood that.
__________________
Jerry & Carol Pearson (+ fur babies) FullTime since 2012 04 Winnebago Adventure, 06 Grand Marquis www.waggintailsrv.com
Jerry, #6 wire in conduit will get you a 70' run of wire at a 2.58% voltage drop. (50 amps)
__________________
Jack & Danielle Mayer PLEASE USE EMAIL TO COMMUNICATE
http://www.jackdanmayer.com, 2009 Volvo 780 HDT, 2015 New Horizons 45'Custom 5th, smart car New Horizons Ambassadors - Let us help you build your dream RV.....