Hi Everyone. Well, after 15 years the RV-Dreams Community Forum is coming to an end. Since it began in August 2005, we've had 58 Million page views, 124,000 posts, and we've spent about $15,000 to keep this valuable resource for RVers free and open. But since we are now off the road and have settled down for the next chapter of our lives, we are taking the Forum down effective June 30, 2021. It has been a tough decision, but it is now time.
We want to thank all of our members for their participation and input over the years, and we want to especially thank those that have acted as Moderators for us during our amazing journey living and traveling in our RV and growing the RV-Dreams Family. We will be forever proud to have been founders of this Forum and to have been supported by such a wonderful community. Thank you all!!
We smelled something burning. Shut down appliances. Found the short when I disconnected to leave. We have a master breaker and separate ones for appliances. I think one of those should have blown but maybe it was outside of that circuit, and a part of the site's power supply? Any thoughts on how to stop this?
Replace both the male and female connectors. The burned up blade or receptacle wasn't making good contact hence resistance = heat. Breakers won't trip as the current never exceeded the breakers rating.
I agree with Bill this looks like a high-resistance connection issue. This looks to be a 30 amp plug, were you by any chance plugged into 50 amp service and the main breaker didn't trip? Are the contacts on the plug (the cord side) corroded? If they are that is likely the cause. You might also want to check if any screw connections on the back of the plug are loose. Whatever the issue is, I would replace both this receptacle and the plug that goes into it as I would bet both are damaged.
-- Edited by arcaguy on Thursday 2nd of August 2018 03:18:26 PM
There was a loose connection either on the plug or back of the receptacle. I tighten all of our power connections about every 6 months. Just be sure to have the power off before sticking a screwdriver on the terminal connection!
Thanks for the replies. To answer one question: the male-end of the power cord can only fit a 30 Amp outlet.
This is true, but there are adapters, referred to by many RV'ers as "dogbones," which have a female receptacle for the end of your power cord but has a 50 amp plug for plugging into a 50 amp socket at the power box. They also have adapters that do the reverse. Many of us with 50 amp carry those adapters. Oddly enough, I still have two 30 amp extension cords stored away in a tub in our basement.
To top it all of, there are also "dogbones" that plug into a 30 amp receptacle that allow a 20 amp cord to be plugged into the other end. And, some adapters allow one to plug a 30 amp power cord into a receptacle on a portable generator.
Good point and I do have and have used the adaptor for a 20 Amp outlet. However, this was not the case here. Also, thanks for the term "dogbone" I will have to add that to my RV vocab!
Sorry that I did not close this out sooner, but BART was correct. The wires on the back were not tightened. And for Bill's suggestion. The male and female connections have been replaced.