Hi Everyone. Well, after 15 years the RV-Dreams Community Forum is coming to an end. Since it began in August 2005, we've had 58 Million page views, 124,000 posts, and we've spent about $15,000 to keep this valuable resource for RVers free and open. But since we are now off the road and have settled down for the next chapter of our lives, we are taking the Forum down effective June 30, 2021. It has been a tough decision, but it is now time.


We want to thank all of our members for their participation and input over the years, and we want to especially thank those that have acted as Moderators for us during our amazing journey living and traveling in our RV and growing the RV-Dreams Family. We will be forever proud to have been founders of this Forum and to have been supported by such a wonderful community. Thank you all!!

Members Login
Username 
 
Password 
    Remember Me  
Post Info TOPIC: An "on generator" question:


RV-Dreams Family Member

Status: Offline
Posts: 70
Date:
An "on generator" question:


Ms. Irma gave me the "opportunity" to run my generator for an extended period of time.  On my toyhauler (2016 Fuzion 416) I have 2 A/C units.  One over the garage (rear) & one over the bedroom (front).  When my "opportunity" came to be on generator, the rear A/C is the only one that worked.
 
I know we can't run both A/Cs at the same time on generator, so I started with both off.  I turned on the front A/C, waited awhile & nothing.  I turned off the front, switched on the rear & voilà!  Spent the nights sleeping in the garage.
 
My thinking is that from the factory only one unit is connected to the generator.   I believe my rig is wired wrong.
 
Can anyone confirm or deny this?  AND if I'm right, how do I make it so the living area is A/C'd under generator power & not my workshop?
 
Signed,
an acquaintance of Ms. Irma!


__________________

Livin' the Life!
In a 43' 2016 Fuzion 416 Toyhauler, towed by 2015 RAM 3500



RV-Dreams Family Member

Status: Offline
Posts: 3721
Date:
An


Are their breakers on the generator itself? Mine has two breakers, one for each leg of 50AMP, and they are tied together. Yours might not be tied together, so only one leg is getting power.

__________________

Bill Joyce,
40' 2004 Dutch Star DP towing an AWD 2020 Ford Escape Hybrid
Journal at http://www.sacnoth.com
Full-timing since July 2003



RV-Dreams Family Member

Status: Offline
Posts: 93
Date:

You did not state what size generator it was. As Mr Joyce noted check breakers. Could be breaker(s) on generator and on the hauler.
Not sure about this suggestion so take it with a grain so salt. Is it one thermostat that controls multi zones in toy hauler?
Good luck

__________________

Jim. KM5J

2014 6.7L Ram 3500, 2008 Excel w 280 watts of solar , 2012 Jack Russel.

Living the dream!



RV-Dreams Family Member

Status: Offline
Posts: 70
Date:

I got it working everyone, thanks for all the helpful input. Toggling the 2 breakers on the gen. did the trick.

__________________

Livin' the Life!
In a 43' 2016 Fuzion 416 Toyhauler, towed by 2015 RAM 3500



RV-Dreams Family Member

Status: Offline
Posts: 1122
Date:
An "on generator" question:


Glad you got it sorted out ... my 5.5KW LP Generator runs everything in the rig ... both AC's and microwave all at the same time😄



-- Edited by RonC on Wednesday 20th of September 2017 04:55:44 PM

__________________

Ron and Janice

 

2016 Ford F350, King Ranch, DRW, 4x4, CC, 6.7 PS Diesel, remote control air lift system

2017 Durango Gold 381REF, Lambright furniture, MCD shades, morRYDE IS, 8K Disc brakes, GY G114  LR H Tires, 27,320 lbs CGVW

FT class of 2016

Page 1 of 1  sorted by
 
Quick Reply

Please log in to post quick replies.

Tweet this page Post to Digg Post to Del.icio.us